| Differential Mode Filter for Fluorescent Lighting Applications |

UL Listed
Catalog Data Sheet
Printer friendly version
|
|
 |
FL Series
- Specifically designed for fluorescent lights
- Suitable for industrial environments
- UL Listed for aftermarket installation
Ordering Information

Available Part Numbers
Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.
|
|
Specifications
| Maximum leakage current, each Line to Ground: |
| |
@ 125 VAC 60 Hz |
3.0 mA |
| |
@ 280 VAC 50 Hz |
6.0 mA |
| |
|
|
| Hipot rating (one minute): |
| |
Line to Ground |
1560 VAC |
| |
Line to Line |
1560 VAC |
| |
|
|
| Operating Frequency: |
50 / 60 Hz |
| |
|
|
| Rated voltage: |
125 / 280 VAC |
| |
|
|
| Rated Current: |
3.9 Amps |
| Operating Ambient Temperature Range (at rated current Ir): |
| |
|
-10°C to +40°C |
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45
|
Electrical Schematic

|
Case Styles

|
|
Case Dimensions
| Part No. |
A |
B |
C |
D |
E |
| (max.) |
(max.) |
(max.) |
± .015 |
(max.) |
| ± .38 |
| 3FL3 |
3.35 |
2.07 |
1.16 |
2.938 |
2.57 |
| 85.09 |
52.58 |
29.5 |
74.63 |
65.3 |
|
|
Performance Data
| Typical Insertion Loss |
| Measured in closed 50 ohm system |
| |
3FL3

|
|
|
| |
| Minimum Insertion Loss in dB: |
| Measured in closed 50 ohm system |
| |
|
|
| Differential Mode / Symmetrical (Line to Line) |
|
|
|
|
|
| Current Rating |
Frequency - MHz |
| .15 |
.3 |
.6 |
1 |
4 |
10 |
20 |
|
| 3.9 A |
10 |
18 |
34 |
46 |
56 |
38 |
26 |
|
|
|
|
|
| USA Customer Service: |
1-800-468-2023 |
| Corcom Products Direct: |
1-847-680-7400 |
| Germany: |
49-89-6089-0 |
|
|
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. |