B Series
The B series RFI power line filters are general purpose common-mode filters effectively providing RFI control of line-to-ground noise in a small size at low cost. These filters are designed to meet a wide variety of electronic and electrical applications and are available in a broad selection of current ratings and termination styles.
The EB models meet the very low leakage current requirements of VDE portable equipment, and (120 Volt) UL544 non-patient medical equipment.
Electrical Schematic
Resistor location for reference only |
Specifications
| Maximum leakage current, each line to ground: |
| |
|
VB Models |
EB Models |
| |
@ 120 VAC 60 Hz: |
.4 mA |
.21 mA |
| |
@ 250 VAC 50 Hz: |
.7 mA |
.36 mA |
| |
|
|
| Hipot rating (one minute): |
| |
line to ground |
2250 VDC |
| |
line to line |
1450 VDC |
| |
|
|
| Operating Frequency: |
50 / 60 Hz |
| |
|
|
| Rated voltage (max.): |
250 VAC |
| |
|
|
| Rated Current: |
1A to 30A |
| |
* refer to part number for rating |
| Minimum insertion loss in dB: |
| Line to ground in 50 ohm circuit |
|
| Current Rating |
Frequency - MHz |
| .15 |
.5 |
1 |
5 |
10 |
30 |
|
| VB Models |
|
|
|
|
|
|
| 1A, 3A |
15 |
30 |
38 |
50 |
50 |
50 |
| 2A, 5A, 10A, 20A, 30A |
7 |
20 |
25 |
40 |
45 |
48 |
|
| EB Models |
|
|
|
|
|
|
| 1A, 3A |
15 |
29 |
35 |
45 |
45 |
48 |
| 2A, 5A, 10A, 20A, 30A |
7 |
19 |
23 |
34 |
37 |
42 |
|
| |
|
Case Styles
B1
| Typical Dimensions |
| Terminals (5) |
.250 |
Holes (4) |
.07 Dia. |
| 6.35 |
1.8 |
| Slot |
.07 x .16 |
Mounting Holes (2) |
.188 Dia |
| 1.8 x 4.1 |
4.78 |
B3

| Typical Dimensions |
| Wire Leads Min. |
4.0 |
Mounting Holes (2) |
.188 Dia |
| 101.6 |
4.78 |
10VB6 & 20VB6

| Typical Dimensions |
| Torque |
18.2 iin. lb. |
Mounting Holes (2) |
.188 Dia |
| 4.78 |
30VB6

|
Case Dimensions
| Part No. |
A |
B |
C |
D |
E |
| (max.) |
(max.) |
(max.) |
± .015 |
(max.) |
| ± .38 |
1VB1, 1EB1,
2VB1, 2EB1
|
2.25 |
1.82 |
0.66 |
2.125 |
2.53 |
| 57.2 |
46.2 |
16.8 |
53.98 |
64.3 |
|
1VB3, 1EB3,
2VB2, 2EB3 |
0.96 |
1.82 |
0.66 |
2.125 |
2.53 |
| 24.4 |
46.2 |
19.8 |
53.98 |
64.3 |
|
3VB1, 3EB1,
5VB1, 5EB1 |
2.61 |
1.82 |
0.78 |
2.125 |
2.53 |
| 66.3 |
46.2 |
19.8 |
53.98 |
64.3 |
|
3VB3, 3EB3
5VB3, 5EB3 |
1.32 |
1.82 |
0.78 |
2.125 |
2.53 |
| 33.5 |
46.2 |
19.8 |
53.98 |
64.3 |
|
| 10VB1, 10EB1 |
2.61 |
1.82 |
1.16 |
2.125 |
2.53 |
| 66.3 |
46.2 |
29.5 |
53.98 |
64.3 |
|
| 10VB3, 10EB3 |
1.32 |
1.82 |
1.16 |
2.125 |
2.53 |
| 33.5 |
46.2 |
29.5 |
53.98 |
64.3 |
|
| 10VB6 |
2.72 |
1.82 |
1.16 |
2.125 |
2.53 |
| 69.1 |
46.2 |
29.5 |
53.98 |
64.3 |
|
| 20VB1, 20EB1 |
3.36 |
2.07 |
1.16 |
2.375 |
2.81 |
| 85.3 |
52.6 |
29.5 |
60.33 |
71.4 |
|
| 20VB6 |
3.46 |
2.07 |
1.16 |
2.375 |
2.81 |
| 87.9 |
52.6 |
29.5 |
60.33 |
71.4 |
|
| 30VB6 |
5.34 |
3.38 |
1.53 |
3.750 |
4.20 |
| 135.6 |
85.9 |
38.9 |
95.3 |
106.7 |
|
Part Numbers
Click on any part number for distributor stock status and eCommerce Links. For more information refer to the Corcom Part Numbering System reference.
|