Skip to content
 |  Tyco Electronics Segment Indicator  |   | 
Tyco Electronics - Our commitment. Your advantage.
Visit www.tycoelectronics.com Corcom Products
Home > Series > PEM > J

J Series

Voltage Selecting and Fused Connector with Optional RFI Power Line Filter for General Purpose Applications for UL544 Health Care Equipment

UL Recognized
CSA Certified

Catalog Data Sheet

J Series

The most widely accepted of all the power entry modules, the J series combines an IEC connector, 2-voltage, or 4- voltage selection, and a North American fuseholder. It features a compact snap-in design and a unique voltage selector card.

J4 Models - This general purpose filter provides susceptibility protection from line-to-ground noise on the power line and acts as a high frequency “clean-up” filter for more complex emissions applications.

HJ4 Models - This medical filter provides susceptibility protection without the leakage current associated with lineto- ground capacitors. Designed to allow equipment to meet UL544 medical specifications for patient care and non-patient care equipment, the HJ filter has a maximum leakage current of 2μA at 120 VAC 60 Hz. See Appendix C for more information on medical applications and UL standards.

Equipment rating labels and mounting clips for thicker panel widths are available as accessories.

See Appendix C for more information on UL544 or UL2601 health care applications.

Note: When using the models with an IEC connector, remember that the leakage current of the companion line cord, GA400, is more significant than that of the filter - which may disqualify this line cord from use in patient care applications.

 

Electrical Schematic

Filtered 6J4 & 6J4-2

click on image for larger view

Filtered 6HJ4-4 & 6HJ4-2

click on image for larger view

Note 1: Jumper required if only SPST power switch is used
Note 2: Jumpers required if no input filtering is used
Note 3: Use only 120V and 240V positions for 2-volt selection units

Resistor location for reference only

Specifications

Maximum leakage current, each line to ground:
    6J4
Models
6EHJ4
Models
6VJ
Models
  @ 250 VAC 50 Hz
500 µA 5 µA 5 µA
     
Hipot rating (one minute):
  line to ground (VAC) 2250 2250 1550
  line to line (VDC) 1450 1450 1450
     
Operating Frequency: 50 / 60 Hz
     
Operating voltages:
  6VJ1, 6J1, 6HJ4-4 100, 120, 220, 240 VAC
  6J1-2, 6J4-2, 6HJ4-2 115, 230 VAC
     
Rated Current: 6 Amps
   
Fuse (not included):

Integral fuse holder, line side accepts .25" x 1.25" fuse

   
Terminals: Connector block terminals .045" square, suitable for solder, wire wrapping, or crimp-on-lugs
   
  † Filtered models only
Minimum insertion loss in dB:
Line to ground in 50 ohm circuit

Current Rating Frequency - MHz
.15 .5 1 5 10 20 30

J4 Models
6A 9 20 25 41 45 45 48
HJ4 Models
6A 9 11 15 19 13 12 10

Case Styles

Unfiltered Models

Filtered Models

Recommended Panel Cutouts

* ± .003

Note 4: Fuse cover door shown in open condition.
Note 5: Standard units mount in panel thickness of .060 - .090"
Special mounting clips sold seperately for panel thickness of .105"-.125"

Voltage Selection

Open cover door and rotate fuse-pull lever to left. Select operating voltage by orienting voltage selection card, desired voltage on top left side. Push card firmly into module slot. Rotate fuse-pull lever back into normal position and re-insert fuse into holders. Use caution in selecting correct fuse value.

 

Case Dimensions

Part No. A B C D
(max.) (max.) (max.) (max.)

Unfiltered
6VJ1, 6VJ1-2

2.68 1.52 1.17 1.23
68.1 38.6 29.7 31.2

Filtered
6J4, 6J4-2
2.75 1.87 1.17 1.58
69.9 47.5 29.7 40.1

6HJ4-4, 6HJ4-2 2.75 1.87 1.17 1.58
69.9 47.5 29.7 40.1

 

Part Numbers

Click on any part number for distributor stock status and eCommerce Links. For more information refer to the Corcom Part Numbering System reference.

Unfiltered Models

Part Number Available Voltage Selection
Positions
6VJ1 4
6VJ1-2 2

Unfiltered Models

Part Number Available Voltage Selection
Positions

RFI Filter
Type

6J4 4 General Purpose ¹
6J4-2 2 General Purpose ¹
6HJ4-4 4 Medical²
6HJ4-2 2 Medical²

 
Note 1: General purpose filter for susceptibility applications
Note 2: Medical line filter for very low leakage UL544 health care requirements

Accessories

Equipment Rating Labels

Unfiltered and Filtered Models Self-adhesive labels, as shown below, are available in multiples of 40 (except JA419). Specify part number in matrix below.


Part
Number
A
VA Max.
B
Fuse
100/120(115)
C
Fuse
220/240(230)

JA410 25 250 mA 125 mA
JA411 50 500 mA 250 mA
JA412 100 1A 500 mA
JA413 200 2A 1A
JA414 250 2.5A 1.25A
JA415 300 3A 1.5A
JA416 400 4A 2A
JA417 500 5A 2.5A
JA418 600 6A 3A
JA419 Assortment, 5 of each label JA410-418

Label Height: .210"
Label Width: 2.330"

Additional Accessories

Line Cord: GA400
2 Voltage Selector Card: JA302
Comes standard with 6VJ1-2, 6J4-2, 6HJ4-w
4 Voltage Selector Card: JA304
Comes standard with 6VJ1, 6J4, 6HJ4-4
Mounting Clips for .105-.125"
Panel Thickness
JA403
Voltage Selector Card
Extractor Tool
JA500
   
   
   

USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.