A Series
The 3-phase filters are designed for 3-phase, four wire, WYE applications providing filtering in each of the three lines plus the neutral and ground line.
The 3-phase models feature:
- Both common mode and differential mode suppression from 50 kHz to 30 MHz
- Effective for both balanced and unbalanced three phase loads
- Ground choke included
- Shielded construction
The dual stage AYT provides higher performance, while the single stage AYP is good for lower noise environments.
Electrical Schematic
AYP6C Models

AYT6C Models

Resistor location for reference only |
Specifications
| Maximum leakage current, each line to ground: |
| |
@ 120 VAC 60 Hz |
1.4 mA |
| |
@ 250 VAC 50 Hz |
3.4 mA |
| |
|
|
| Hipot rating (one minute): |
| |
line to ground |
1500 VAC |
| |
neutral to ground |
1500 VAC |
| |
line to neutral |
1450 VDC |
| |
|
|
| Operating Frequency: |
50 / 60 Hz |
| |
|
|
| Rated voltage (max.): |
|
| |
phase to phase |
440 VAC |
| |
phase to neutral / ground |
250 VAC |
| |
|
|
| Rated Current: |
20A to 60A * |
| |
* refer to part number for rating |
| Minimum insertion loss in dB: |
| Line to ground in 50 ohm circuit |
|
| Current Rating |
Frequency - MHz |
| .05 |
.1 |
.15 |
.5 |
1 |
5 |
10 |
30 |
|
| AYP6C |
| 20A |
22 |
32 |
39 |
55 |
56 |
65 |
65 |
54 |
| 30A |
15 |
24 |
30 |
55 |
55 |
61 |
63 |
50 |
| 45A |
8 |
19 |
25 |
49 |
49 |
56 |
58 |
45 |
| 60A |
5 |
16 |
22 |
50 |
50 |
54 |
54 |
47 |
| AYT6C |
| 20A |
45 |
63 |
70 |
75 |
75 |
75 |
75 |
65 |
| 30A |
29 |
53 |
61 |
75 |
75 |
75 |
75 |
60 |
| 45A |
15 |
39 |
43 |
75 |
75 |
75 |
75 |
50 |
| 60A |
12 |
37 |
46 |
75 |
75 |
75 |
70 |
45 |
|
| Line to line in 50 ohm circuit |
|
| Current Rating |
Frequency - MHz |
| .05 |
.1 |
.15 |
.5 |
1 |
5 |
10 |
30 |
|
| AYP6C |
| 20A |
20 |
38 |
50 |
65 |
65 |
65 |
60 |
52 |
| 30A |
18 |
28 |
43 |
65 |
65 |
65 |
59 |
48 |
| 45A |
8 |
20 |
27 |
60 |
65 |
65 |
56 |
43 |
| 60A |
20 |
24 |
27 |
60 |
65 |
65 |
56 |
50 |
| AYT6C |
| 20A |
27 |
56 |
65 |
70 |
70 |
70 |
70 |
70 |
| 30A |
17 |
46 |
55 |
75 |
75 |
75 |
75 |
70 |
| 45A |
14 |
41 |
50 |
75 |
75 |
75 |
75 |
65 |
| 60A |
26 |
50 |
58 |
75 |
75 |
75 |
75 |
60 |
|
| |
|
Case Styles
AYP6C & AYT6C
End Bell Mounting Accessories
Mounting brackets available in two sizes, 20/30 amp (AA400) and 45/60 amp (AA405).

AA400/405
End Bell mounting kits available in two sizes, 20/30 amp (AA406) and 45/60 amp (AA407)

AA406/407
10 pack of additional captive nuts to mount filter: AA401
|
Case Dimensions
| Part No. |
A* |
B |
C |
D |
E |
| (max.) |
(max.) |
(max.) |
± .030 |
± .015 |
| ± .76 |
± .38 |
20AYP6C
30AYP6C |
8.82 |
5.57 |
2.56 |
4.616 |
1.50 |
| 224.0 |
141.5 |
65.0 |
117.2 |
38.1 |
|
45AYP6C
60AYP6C |
9.43 |
6.92 |
4.82 |
5.950 |
3.75 |
| 239.5 |
175.8 |
122.4 |
151.1 |
95.3 |
|
20AYT6C
30AYT6C |
13.82 |
5.57 |
2.56 |
4.616 |
1.50 |
| 351.0 |
141.5 |
65.0 |
117.2 |
38.1 |
|
45AYT6C
60AYT6C |
13.83 |
6.92 |
4.82 |
5.950 |
3.75 |
| 351.3 |
175.8 |
122.4 |
151.1 |
95.3 |
|
| * For end bell covering terminals and connections, add: |
| 20A & 30A |
5.57 |
|
| 141.48 |
| 45A & 60A |
6.45 |
| 163.83 |
Part Numbers